Common Vaillant Boiler Problems: Causes, Checks and Fixes
Hertfordshire, Bedfordshire & Cambridgeshire
The most common Vaillant boiler problems are low system pressure (F.22), the boiler failing to light or losing its flame (F.28 and F.29), overheating or poor circulation (F.20, F.23, F.75 and F.83), fan faults (F.32) and hot water problems on combis. Most homeowners can safely check the pressure, the gas supply, the condensate pipe and the controls, but anything inside the boiler case needs a Gas Safe registered engineer.
- Low pressure is the most common Vaillant problem, and Vaillant says the pressure should sit between 1.0 and 2.0 bar with the heating cold.
- F.28 and F.29 mean the boiler cannot light or keep its flame, often because of the gas supply or a frozen condensate pipe.
- F.20, F.23, F.75 and F.83 usually point to water not circulating properly: air, sludge, the pump or a sensor.
- Poor hot water on a combi is often limescale or a diverter valve, and hard water across most of Hertfordshire makes scale common.
- Press reset two or three times at most. If the code keeps coming back, book an engineer.

Vaillant boiler problems at a glance
Vaillant boilers, including the ecoTEC plus, ecoTEC pro and ecoFIT pure, show a fault code beginning with F when something stops them working. The table below groups the most common problems.
| Problem | Codes you may see | Usual causes | Can you check it yourself? |
|---|---|---|---|
| Low or falling pressure | F.22 | Pressure lost after bleeding, a leak, a faulty pressure relief valve or expansion vessel | Yes, read the gauge and top up with the filling loop |
| Boiler will not light | F.28 | Gas supply, empty prepay meter, frozen condensate pipe, ignition or gas valve fault | Partly: gas supply, meter and condensate pipe |
| Boiler lights then goes out | F.29 | Gas supply interruption, blocked condensate, flue gases drawn back in | Partly: gas supply, meter and condensate pipe |
| Overheating or poor circulation | F.20, F.23, F.75, F.83 | Air, sludge, low pressure, pump, diverter valve or sensor | Partly: pressure and bleeding radiators |
| Fan fault | F.32 | Fan, fan wiring, blocked flue or air intake | Only a look at the flue outside |
| Electronics and flame monitoring | F.27, F.61, F.62 | Moisture, gas valve, circuit board or electrode | No, one reset only |
| Poor or no hot water | Often no code | Diverter valve, scaled plate heat exchanger, flow sensor | Check the boiler is not in heating-only mode |
Our boiler repair service covers every Vaillant model, old and new.
Low pressure and pressure that keeps dropping
A sealed heating system needs enough water pressure for the pump and heat exchanger to work safely. Vaillant’s user guides say the pressure should be between 1.0 and 2.0 bar with the heating cold, and the boiler shuts down and shows F.22 if it falls below 0.5 bar. On current models the display shows the pressure as a bar graph or a number.
Topping up with the filling loop clears most one-off F.22 faults. It is normal to lose a little pressure after bleeding radiators. What is not normal is having to top up every week or two. That points to a leak somewhere on the system, a pressure relief valve letting water out through the pipe outside, or an expansion vessel that has lost its air charge. Our guide to the Vaillant F22 fault code walks through the top-up step by step.
The boiler will not light or keeps locking out
F.28 means the boiler tried to light and did not detect a flame. Vaillant’s user guides say it makes three attempts before locking out. F.29 means it was running, lost its flame and could not relight.
Is the gas hob working? Has a prepayment meter run out of credit? Is the white plastic condensate pipe outside frozen, which happens in cold snaps and stops the boiler firing? If all of those are fine, the cause is usually inside the boiler: the ignition electrode, the ignition lead, the gas valve, the fan or the flue. The Vaillant F28 guide covers the full list, including how to thaw a frozen condensate pipe safely with warm water.
Overheating and circulation faults
Several Vaillant codes are really the same message: water is not moving through the boiler the way it should.
- F.20 means the safety cut-out has closed the gas valve because the flow or return temperature went above its limit.
- F.23 means the temperature difference between the water leaving and returning to the boiler is too great.
- F.75 means the boiler did not see the small pressure rise it expects when the pump starts.
- F.83 means the temperature sensors saw little or no change when the burner started, so the boiler assumes there is not enough water in the heat exchanger.
The causes overlap: low pressure, air trapped in the boiler or radiators, sludge restricting flow, a pump that is weak or seized, a sticking diverter valve, or a faulty sensor. You can check the pressure and bleed the radiators. If the code returns, an engineer needs to test the pump and sensors and look at the condition of the system water. Where sludge is the root cause, a power flush may be part of the fix.
Fan and flue faults
F.32 is a fan fault: the fan speed is outside the range the boiler expects, so it will not light. The fan sits inside the sealed case, so this is engineer work. You can check the flue terminal outside is not blocked, but do not poke anything into it.
Hot water problems on Vaillant combis
A combi boiler switches between heating and hot water using a diverter valve. When that valve sticks, you can end up with heating but no hot water, hot water that is only lukewarm, or radiators warming up when you run a tap.
Hot water that swings between hot and cold, or that has become weak, is often limescale in the plate heat exchanger, the small heat exchanger that heats your tap water. Most of Hertfordshire has hard water, so scaling is a common cause in this area. A faulty flow sensor can also stop the boiler recognising that a tap is open. Our guide to no hot water but the heating works explains how to tell these apart.
Noises: kettling, gurgling and banging
- Kettling (a rumbling, boiling sound) usually means scale or sludge on the heat exchanger is causing local overheating.
- Gurgling usually means air in the system or low pressure. Bleed the radiators and recheck the pressure.
- Humming or droning can come from the pump.
- Banging or clicking at ignition can be a delayed ignition, which needs an engineer straight away.
Electronics and flame monitoring faults
F.27 means the boiler has seen a flame signal while the burner should be off. Vaillant calls this flame simulation, and it can be caused by moisture on the electronics, a fault in the flame monitoring or a gas valve that is not sealing. F.62 means the flame took too long to go out when the gas valve was told to close. F.61 is a fault in the boiler’s control electronics, and on many ecoTEC models it relates to the circuit that drives the gas valve. All three are safety lockouts. Try one reset, and if the code returns, leave the boiler off and book a repair.
Check these first
These checks are safe for a homeowner and follow Vaillant’s own user guidance.
- Note the code. Write down exactly what the display shows, including any number next to it.
- Check the pressure. With the heating cold, it should be between 1.0 and 2.0 bar. If it is below 1.0 bar, top up with the filling loop as the user guide describes.
- Check the gas. Make sure other gas appliances work and a prepay meter has credit.
- Check the condensate pipe. In freezing weather, pour warm (not boiling) water along the outside section.
- Check the controls. Make sure the thermostat is calling for heat, the timer is on, and the fused spur next to the boiler is switched on.
- Reset once or twice. Press the reset button (Vaillant calls it the fault clearance key). If the code comes back after two or three tries, stop.
What not to do
- Do not remove the boiler casing or touch anything inside it. Under the Gas Safety (Installation and Use) Regulations 1998, only a Gas Safe registered engineer may work on a gas appliance.
- Do not keep pressing reset. Repeated resets on a lockout fault can make things worse.
- Do not use boiling water on a condensate pipe, which can crack the plastic.
- If you smell gas, open windows, do not use electrical switches, turn off the gas at the meter if it is safe to do so and call the National Gas Emergency Service on 0800 111 999.
What an engineer will check
A Gas Safe engineer will read the fault history stored in the boiler, then test the relevant parts: the pressure sensor and expansion vessel for pressure faults, the electrode, gas valve and gas pressure for ignition faults, the pump, sensors and diverter valve for circulation faults, and the fan and flue for F.32. After any repair that touches the gas or combustion side, they will carry out a combustion check with a flue gas analyser.
Repair or replace?
Most Vaillant faults are worth repairing, because electrodes, sensors, pumps, diverter valves and expansion vessels are routine parts. Replacement starts to make sense when the boiler is old, a major part such as the main heat exchanger or circuit board has failed, or the same faults keep returning. Our guide to repair or replace sets out how we weigh it up.
If you do replace it, we are a Vaillant myREWARDS installer, which means manufacturer guarantees of up to 10 years on selected Vaillant boilers. Our new boiler packages include a magnetic system filter, the first year’s service and removal of the old boiler. See our Vaillant boiler installation page for more.
What we charge to fix it
Our prices, before you ring
| Weekday repair visit, Monday to Friday 8am to 5pm, no call-out fee | £150 + VAT £180 inc VAT |
| Evenings and weekends, first hour including the call-out | £297.60 inc VAT |
| Overnight, first hour including the call-out | £330 inc VAT |
| If a new boiler is the better answer, fitted | from £2,780 inc VAT |
The weekday visit is a fixed price. A Gas Safe engineer comes out, finds the fault and does any small fix that needs no parts, with up to an hour on site. If the repair needs parts or more time, you get a fixed price before anything else is done. We cover Hertfordshire, Bedfordshire, Cambridgeshire and North London. Book a boiler repair, see every rate, or get a new boiler price online.
Frequently asked questions
Are Vaillant boilers reliable?
Yes, Vaillant boilers are generally well regarded and parts are widely available. Like any boiler, they are more reliable when they are serviced every year and the system water is kept clean, with inhibitor and a magnetic filter.
How do I reset a Vaillant boiler?
Press the reset button, which Vaillant calls the fault clearance key, and give the boiler a few minutes to try again. If the fault returns after two or three resets, stop and call a Gas Safe engineer rather than resetting it again.
Why does my Vaillant boiler keep losing pressure?
A little pressure loss after bleeding radiators is normal. If you need to top up regularly, there is usually a leak on the system, a pressure relief valve letting by, or an expansion vessel that has lost its charge, and an engineer needs to find which.
How long does a Vaillant boiler last?
A well-installed and regularly serviced boiler commonly lasts 10 to 15 years, and sometimes longer. Hard water, sludge and missed services all shorten that.
Can I fix a Vaillant fault code myself?
You can deal with low pressure, a frozen condensate pipe, an empty prepay meter and control settings yourself. Anything that needs the case removed, such as a pump, sensor, fan or gas valve, must be done by a Gas Safe registered engineer.
Vaillant boiler help in Hertfordshire, Bedfordshire and Cambridgeshire
Our Gas Safe registered engineers (registration 956889) repair and service all Vaillant models from fully stocked vans, and the phone is answered 24 hours a day, 7 days a week. See our boiler repair page or call 01462 506374.
What our customers say
Speak to a local engineer
Vantage Plumbing and Heating covers Hertfordshire, Bedfordshire and the surrounding areas. Call and talk to an engineer, or send us the details and we will come back to you with a price.
Gas Safe registered, number 956889. Emergency line answered 24/7.
Boiler engineers near you
Boiler playing up? Book a local Gas Safe engineer
We cover Hertfordshire, Bedfordshire and Cambridgeshire. Choose your town:
Not listed? See all the areas we cover or call 01462 506 374