Glow-worm Boiler Fault Codes: Full List and What to Do
Hertfordshire, Bedfordshire & Cambridgeshire
A Glow-worm boiler fault code is an F followed by a number, such as F.22 or F.28, and it tells you which safety check has failed and why the boiler has stopped. A few codes, mainly F.22 (low water pressure), F.28 (failed to light) and F.29 (flame lost), often have simple causes a homeowner can check, but most codes point to a sensor, fan, gas valve or electronics fault that needs a Gas Safe registered engineer.
- Glow-worm codes start with F. Status codes starting with S show what the boiler is doing and are not faults.
- F.22 means low water pressure. You can often fix it by topping up the pressure with the filling loop.
- F.28 and F.29 often come from a gas supply problem or a frozen condensate pipe in winter.
- Press reset once, or a few times at most if the manual allows it. If the code keeps returning, call an engineer.
- Older Glow-worm ranges can use different meanings for the same number, so check the manual for your model.
How Glow-worm fault codes work
Glow-worm boilers constantly monitor temperatures, water pressure, fan speed, the flame and the gas valve. When a reading is outside safe limits, the boiler shuts down and shows a code starting with F. Some faults clear once the problem goes away. Others lock the boiler out until someone presses reset.
Current Glow-worm boilers, such as the Energy, Ultimate and Essential ranges, use a common set of codes, and the boiler stores recent faults in its memory so an engineer can see what has happened. Glow-worm is part of the same group as Vaillant, so many codes match Vaillant’s, but always check against the Glow-worm manual for your model.
Codes beginning with S are status codes. They show the boiler’s current operating mode, for example heating or hot water, and are not faults. If you see an S code, the boiler is usually just telling you what it is doing.
If your boiler shows a fault you cannot clear, our boiler repair engineers repair and service all the major brands, including Glow-worm.
The codes you are most likely to see
| Code | What it means | Can you do anything? |
|---|---|---|
| F.22 | Low water pressure in the boiler | Yes, top up the pressure. See our Glow-worm F22 guide |
| F.28 | The boiler failed to light when starting up | Yes, check the gas supply and condensate pipe. See our Glow-worm F28 guide |
| F.29 | The flame went out and the boiler could not relight | Yes, same checks as F.28. See our Glow-worm F29 guide |
| F.75 | The boiler did not detect the pressure rise it expects when the pump starts | Check and top up the pressure. See our Glow-worm F75 guide |
| F.20 | Overheat safety cut-out has operated | Check pressure and radiator valves, then engineer |
| F.23 | Temperature difference between flow and return is too great | Check pressure, bleed radiators, then engineer |
| F.24 | Temperature rising too quickly | Check pressure, bleed radiators, then engineer |
| F.32 | Fan speed outside the expected range | Check the flue outside is clear, then engineer |
| F.61 | Gas valve control fault | Engineer only |
Full list of Glow-worm fault codes
This list is based on Glow-worm’s installation manuals for current boilers and the fault code guidance on Glow-worm’s own website. Not every code appears on every model.
| Code | Meaning | Common causes |
|---|---|---|
| F.00 | Flow temperature sensor interrupted | Plug not connected, broken wiring, faulty sensor |
| F.01 | Return temperature sensor interrupted | Plug not connected, broken wiring, faulty sensor |
| F.10 | Flow temperature sensor short circuit | Faulty sensor or wiring short |
| F.11 | Return temperature sensor short circuit | Faulty sensor or wiring short |
| F.13 | Hot water cylinder temperature sensor short circuit | Faulty sensor or wiring |
| F.20 | Safety switch-off, overheat temperature reached | Poor circulation, sensor or connection fault, earthing or ignition lead problems |
| F.22 | Safety switch-off, low water pressure | Low system pressure, faulty pressure sensor, loose pump or sensor wiring |
| F.23 | Safety switch-off, flow and return temperature difference too great | Pump blocked or weak, air in the boiler, sensors swapped |
| F.24 | Safety switch-off, temperature rise too fast | Pump blocked or weak, air, low pressure, non-return valve problem |
| F.25 | On current models, flue gas temperature too high | Safety limiter or wiring fault. On some older ranges F.25 is a circulation fault |
| F.27 | Flame detected when the burner should be off | Damp on the electronics, faulty flame monitoring, gas valve not closing |
| F.28 | Ignition unsuccessful on start-up | No gas or low gas pressure, air in the gas, ignition or electrode fault, condensate blockage |
| F.29 | Flame loss during operation | Gas supply interrupted, flue gas recirculation, earthing or ignition fault, condensate blockage |
| F.32 | Fan speed outside tolerance | Fan plug or wiring, blocked fan, faulty speed sensor, electronics |
| F.33 | Air pressure switch fault | Faulty switch or blocked air intake or flue |
| F.49 | Low voltage on the controls connection (eBUS) | Short circuit or overload on the controls wiring |
| F.61 | Gas valve control fault | Wiring short to the gas valve, faulty gas valve, electronics |
| F.62 | Gas valve switch-off fault | Gas valve slow to close or leaking, electronics |
| F.63 | Memory (EEPROM) fault | Electronics |
| F.64 | Electronics or sensor fault | Sensor short circuit, electronics |
| F.65 | Electronics temperature too high | Heat from outside the boiler, electronics |
| F.67 | Implausible flame signal | Electronics |
| F.68 | Unstable flame signal | Air in the gas, low gas pressure, incorrect gas ratio |
| F.70 | Invalid device code | Display or PCB replaced without being set up |
| F.71 | Flow or return sensor fault | Sensor badly attached or faulty |
| F.72 | Flow and return sensor readings do not agree | Faulty sensor or circulation fault |
| F.73 | Water pressure sensor not connected or short circuited | Wiring fault or faulty sensor |
| F.74 | Electrical problem in the water pressure sensor | Wiring or sensor fault |
| F.75 | No pressure rise detected when the pump starts | Low pressure, air, faulty pressure sensor or pump |
| F.77 | Condensate or flue fault | Flue non-return flap faulty |
| F.83 | Little or no temperature rise when the burner starts | Low pressure, circulation fault, sensor problem |
| F.84 | Implausible flow and return readings | Sensors swapped or badly fitted, pipework fault |
| F.85 | Temperature sensor fitting fault | Sensors on the same pipe or wrongly fitted |
| F.86 | Underfloor heating contact open | Underfloor heating thermostat or wiring |
| F.87 | Ignition electrode fault | Electrode not connected or wiring short |
| F.88 | Gas valve electrical connection fault | Gas valve not connected or wiring short |
| F.89 | Pump fault | Pump not connected, wrong pump fitted or wiring short |
Check these first
These checks are safe for a homeowner. None of them means opening the boiler.
- Write down the code exactly as it appears.
- Check the pressure gauge. With the system cold, it should normally read between about 1 and 1.5 bar. Glow-worm’s manuals say the boiler switches off with F.22 when pressure falls very low. If the gauge is below 1 bar and your user guide shows how to use the filling loop, top it up slowly and close the valves afterwards.
- Check the gas supply. Does the hob light? If you have a prepayment meter, check it has credit. Glow-worm suggests these checks for F.28 and F.29.
- Check the condensate pipe in cold weather. A frozen condensate pipe can cause F.28 and F.29. Thaw it with warm (not boiling) water, as shown in our frozen condensate pipe guide.
- Bleed the radiators if some are cold at the top, then recheck the pressure, because bleeding lowers it.
- Check the flue terminal outside is not blocked by leaves, a bag or plants. Do not touch or remove it.
- Press reset. Glow-worm’s operating instructions allow a reset, and for a failed ignition a few attempts. If the code will not clear, or keeps coming back, stop and call an engineer.
What not to do
- Do not keep resetting a boiler that keeps locking out. The cause is still there.
- Do not remove the casing or touch the gas valve, fan, PCB, electrodes, heat exchanger or flue. Glow-worm advises homeowners not to go inside the boiler, and by law only a Gas Safe registered engineer can work on it.
- Do not top up the pressure above the level your user guide gives, and do not leave the filling loop open.
- If you smell gas, call the National Gas Emergency Service on 0800 111 999, open windows, do not use electrical switches and turn the gas off at the meter if it is safe to do so.
Older Glow-worm boilers
Glow-worm keeps separate fault code information for older ranges, and some older boilers use codes that look the same as current ones but mean something different. F.25 is a good example: on current boilers it is a flue gas temperature fault, but on some older Flexicom and Ultracom boilers it is a circulation fault. If your boiler is more than a few years old, look up the code in the manual for your exact model, or tell the engineer the model name and code.
What an engineer will check
A Gas Safe engineer will read the fault memory, which stores recent codes and when they happened, then work through the causes for that code. Depending on the fault, they will test gas pressure at the boiler, clean and inspect the condensate trap, check the electrodes, test the fan, sensors and wiring, check the pump and pressure sensor, and inspect the flue. Once repaired, they will check combustion and confirm the boiler runs safely.
Repair or replace?
Most Glow-worm faults are repairable. Replacement is worth discussing when the boiler is old, the repair is to a major part such as the heat exchanger, or faults keep coming back.
What we charge to fix it
Our prices, before you ring
| Weekday repair visit, Monday to Friday 8am to 5pm, no call-out fee | £150 + VAT £180 inc VAT |
| Evenings and weekends, first hour including the call-out | £297.60 inc VAT |
| Overnight, first hour including the call-out | £330 inc VAT |
| If a new boiler is the better answer, fitted | from £2,780 inc VAT |
The weekday visit is a fixed price. A Gas Safe engineer comes out, finds the fault and does any small fix that needs no parts, with up to an hour on site. If the repair needs parts or more time, you get a fixed price before anything else is done. We cover Hertfordshire, Bedfordshire, Cambridgeshire and North London. Book a boiler repair, see every rate, or get a new boiler price online.
Frequently asked questions
How do I reset my Glow-worm boiler?
Press the reset button on the boiler’s control panel, as shown in the user guide for your model. Glow-worm’s operating instructions describe pressing it briefly, after which the boiler tries to start again. If the code returns, do not keep resetting it.
Why does my Glow-worm boiler keep showing F.22?
F.22 means the water pressure is too low. If topping up fixes it but it keeps coming back, water is escaping somewhere, often through a leak, the pressure relief valve or a faulty expansion vessel. That needs an engineer to find and fix.
Can I see previous fault codes on my Glow-worm boiler?
Current Glow-worm boilers store recent fault codes in a fault memory, along with when they happened. This is usually read by an engineer, and it helps them spot faults that come and go.
Is it safe to use my Glow-worm boiler with a fault code?
If the boiler has locked out, it has stopped itself for safety and will not run until the fault is cleared. Leave it off if the code will not clear after a reset, and never try to bypass a fault. If you smell gas, call 0800 111 999.
Glow-worm boiler repairs in Hertfordshire, Bedfordshire and Cambridgeshire
If your Glow-worm boiler is showing a code you cannot clear, book our boiler repair team on 01462 506374. We answer the phone 24 hours a day, 7 days a week. Our Gas Safe registration number is 956889, and we are rated 4.9 on Google.
What our customers say
Rather have an engineer look at it?
Call the office, message us on WhatsApp or ask for a callback. We cover Hertfordshire, Bedfordshire and the surrounding areas.
Speak to a local engineer
Vantage Plumbing and Heating covers Hertfordshire, Bedfordshire and the surrounding areas. Call and talk to an engineer, or send us the details and we will come back to you with a price.
Gas Safe registered, number 956889. Emergency line answered 24/7.
Boiler engineers near you
Boiler playing up? Book a local Gas Safe engineer
We cover Hertfordshire, Bedfordshire and Cambridgeshire. Choose your town:
Not listed? See all the areas we cover or call 01462 506 374