Vaillant F02 Fault Code: Hot Water Sensor Fault Explained
Hertfordshire, Bedfordshire & Cambridgeshire
Vaillant F02 (shown as F.02, or F.2 on older models) means the boiler has lost the signal from one of its hot water temperature sensors, an open circuit in the sensor or its wiring. Which sensor depends on the model, so the first step is to identify your boiler, and the fix is a sensor, plug or wiring repair carried out by a Gas Safe registered engineer.
In short
- F02 is a sensor “interruption”: the circuit board is getting no usable signal from a hot water temperature sensor.
- On ecoTEC plus boilers with a built-in actoSTOR hot water store, Vaillant lists F.02 as an interruption in the actoSTOR cylinder charging sensor, shown only together with F.91.
- On Vaillant’s older atmoTEC combi boilers, F.2 means an interruption in the hot water outlet sensor.
- F02 is not a flow sensor fault. On Vaillant boilers that is F.00.
- You can reset once or twice and note the model. The sensor, plugs and wiring need an engineer.

New boiler?
Get an instant estimate for a new boiler
Answer a few questions about your home online and see your estimate straight away, fitted by our own engineers.
What F02 means on a Vaillant boiler
Vaillant boilers use NTC thermistors to measure temperature. An NTC is a small sensor whose resistance falls as it gets warmer, and the circuit board reads that resistance as a temperature. When the board sees an open circuit, where the resistance is effectively infinite, it cannot trust the reading and it raises an interruption code.
The flow and return sensors on the heating side have their own codes (F.00 and F.01). F02 belongs to the hot water side, and this is where the model matters.
| Vaillant model | What F.02 or F.2 means (from Vaillant’s manuals) | What it affects |
|---|---|---|
| ecoTEC plus with actoSTOR (VUI store models) | Interruption in the actoSTOR cylinder charging sensor, only in combination with F.91 | The built-in hot water store and its charging |
| atmoTEC combi (VCW) | Interruption in the hot water outlet sensor | Hot water temperature control |
| Standard ecoTEC plus combi or system boiler | F.02 relates to the actoSTOR module, so it is not expected on models without one | Check the model and exact code carefully |
On the ecoTEC plus, Vaillant’s installation manual describes F.02 as “Interruption cylinder charging sensor actoSTOR (NTC) only in combination with F.91”. The actoSTOR is a hot water store with its own electronics built into certain ecoTEC plus models. The causes Vaillant lists are a faulty sensor, a faulty sensor cable, a bad plug connection at the sensor or a bad plug connection at the actoSTOR electronics.
On the atmoTEC range, an older line of open-flued Vaillant boilers, the installation manual lists F.2 as “Interruption: DHW outlet sensor”. DHW means domestic hot water, so this is the sensor that tells the boiler how hot the water leaving it for your taps is.
You may read elsewhere that F02 is a flow sensor fault. That does not match Vaillant’s manuals, which give the flow sensor interruption its own code, F.00. If you are unsure which model you have, the model name is usually shown on the front of the boiler, and your engineer can read the full type (for example VUI or VUW) from the data plate.
Newer Vaillant controls show codes with three digits, such as F.022 instead of F.22. If yours shows a three-digit code, give the engineer the exact code rather than assuming it matches this page.
Check these first
- Note the exact code and any others. On an actoSTOR model, F.02 should appear with F.91. Write down both, and the model name from the front of the boiler.
- Reset the boiler once. Press the reset button and let the boiler restart. If the code comes back, one more reset at most, then stop.
- Check the power. Make sure the fused spur by the boiler is on and the display is lit.
- Check heating and hot water separately. Note whether you still have heating, hot water, both or neither. It tells the engineer where to start.
- Look for leaks outside the casing. Water dripping onto the boiler or around the hot water store can reach connectors. Do not open anything, just note what you can see.
- Think about recent work. A recent service or repair can leave a plug partly disconnected.
If the code returns, book a Vaillant boiler repair with the model and the codes to hand.
What not to do
- Do not remove the boiler casing or the store cover to look at sensors or plugs. Under the Gas Safety (Installation and Use) Regulations 1998 only a Gas Safe registered engineer may work on a gas appliance.
- Do not keep resetting. A broken sensor circuit will not repair itself.
- Do not turn the hot water temperature to maximum to “test” it. With a sensor out of action, the boiler cannot control the temperature properly.
- If you smell gas, call the National Gas Emergency Service on 0800 111 999, open windows, do not use electrical switches and turn off the gas at the meter if it is safe.
Common causes of F02
| Cause | What you might notice | Can you fix it yourself? | What the engineer does |
|---|---|---|---|
| Failed hot water sensor | Code returns straight after a reset | No | Measures the sensor’s resistance and replaces it |
| Damaged sensor cable | Code may come and go if the cable moves | No | Tests continuity and repairs or replaces the cable |
| Loose plug at the sensor | Code after a service or repair | No | Reseats and inspects the connector |
| Loose plug at the actoSTOR electronics | F.02 with F.91 on a store model | No | Checks the connections on the actoSTOR board |
| Water or corrosion on a connector | Code after a leak near the boiler or store | Only by stopping an external leak | Cleans or replaces the connector, fixes the leak |
| Control electronics fault | Sensor and wiring all test correctly | No | Tests the board or module before replacing anything |
What an engineer will check
- Identify the model and read the fault history. The engineer confirms which boiler you have and looks at the fault list, so they know which sensor F02 refers to.
- Inspect the sensor and its plugs. With the power isolated, they check the sensor is fitted properly and that the plugs at both ends are seated and clean.
- Measure the sensor. Resistance is measured and compared with what Vaillant expects at that temperature. An open circuit or a reading far out of range means the sensor has failed.
- Test the cable. Each core is tested for continuity along its length, looking for breaks, chafing or a pin that has pushed back.
- Check the electronics last. On an actoSTOR model, the store’s electronics and its connection to the main board are checked. The circuit board is only replaced once everything else is proven good.
- Run the hot water. After the repair, the engineer runs hot water and checks the temperature reading is sensible and stable.
Repair or replace?
A hot water sensor fault is almost always worth repairing. Sensors are small parts and wiring repairs are quick. Replacement is only worth discussing if the electronics have failed on an older boiler that already has other problems. Our repair or replace guide sets out how we make that call honestly.
If you are losing hot water but the heating works and there is no code at all, our guide to no hot water but the heating works covers the other common causes.
What it costs with Vantage
In normal working hours there is no call-out fee. Gas faults start with a fixed-price Gas Safe diagnostic visit, and if we can fix it on the same visit, part of that diagnostic charge comes off the repair. After the first hour, time is charged in half-hour steps, and parts are quoted before we fit them. Evening, weekend and overnight visits are charged at the out-of-hours rates. Every rate is published on our prices page, so you know what you will pay before we arrive. Our work comes with a 12 month labour guarantee.
Related Vaillant codes
- Vaillant F20: the overheat safety cut-out has operated.
- Vaillant F23: the temperature difference between flow and return is too great.
- Vaillant F22: low water pressure in the heating system.
Frequently asked questions
Is Vaillant F02 a flow sensor fault?
No. In Vaillant’s manuals the flow sensor interruption is F.00. F02 relates to a hot water sensor: the actoSTOR cylinder charging sensor on ecoTEC plus store models, or the hot water outlet sensor on older atmoTEC combis.
What is F.91 and why does it appear with F02?
On ecoTEC plus models with an actoSTOR store, Vaillant’s manual says F.02 is shown only in combination with F.91. Together they point the engineer at the actoSTOR side of the boiler, its sensors and connections, rather than at the main heating sensors.
Can I still use my heating with an F02 code?
It depends on the model and how the boiler responds, so try the heating and note what happens. Either way, the boiler is protecting itself, and a sensor fault like this should be repaired rather than lived with.
My boiler shows F02 but I do not have an actoSTOR. What now?
Write down the exact code, including any dot and how many digits it has, and the model name. Codes can be misread on small displays, and newer boilers use three-digit codes. An engineer can read the fault list and confirm what the boiler is really reporting.
When to call an engineer
If F02 returns after a reset or two, a Gas Safe registered engineer needs to test the sensor and its wiring. We repair and service Vaillant boilers across Hertfordshire, Bedfordshire and Cambridgeshire, and our phone is answered 24 hours a day, 7 days a week. Book a boiler repair or call 01462 506374.
What our customers say
Speak to a local engineer
Vantage Plumbing and Heating covers Hertfordshire, Bedfordshire and the surrounding areas. Call and talk to an engineer, or send us the details and we will come back to you with a price.
Gas Safe registered, number 956889. Emergency line answered 24/7.
Boiler engineers near you
Boiler playing up? Book a local Gas Safe engineer
We cover Hertfordshire, Bedfordshire and Cambridgeshire. Choose your town:
Not listed? See all the areas we cover or call 01462 506 374