Worcester Bosch A21 Fault Code: What It Means and What to Do
Hertfordshire, Bedfordshire & Cambridgeshire
Worcester Bosch A21 means the wireless room thermostat has lost its radio (RF) link with its receiver, so the boiler is not getting instructions from the thermostat. It is a controls fault rather than a boiler fault, and most of the time it is fixed by changing the thermostat batteries, moving the thermostat to get a better signal or letting the two units reconnect after a power cut.
In short
- Worcester’s instructions for the Greenstar Comfort II RF thermostat list A21 as “loss of RF signal”.
- A21 also shows at first switch-on until the thermostat and receiver have linked up. Allow up to a minute.
- Start with fresh batteries in the thermostat and check the boiler has power.
- Check the signal strength in the thermostat’s Info menu and move the thermostat if the signal is weak.
- If it still will not link, the units may need pairing again, or one of them may be faulty.
- This is not gas work, but anything inside the boiler casing still needs a Gas Safe engineer.
What A21 means on a Worcester Bosch system
Many Worcester Bosch boilers are controlled by a wireless room thermostat. The thermostat sits on a wall in the living area and talks by radio to a receiver, which is either plugged into the boiler’s control panel or mounted on a wall plate nearby. The receiver passes the thermostat’s instructions to the boiler.
If the receiver stops hearing the thermostat, the link is lost and the thermostat shows A21. The installation instructions for the Worcester Greenstar Comfort II RF thermostat describe A21 as a loss of RF signal, and note that A21 is also displayed at initial switch-on until the two units have established a communication link. The same instructions list A22 with the same meaning.
Because the boiler is not getting instructions, you may find the heating does not come on when it should, or does not respond to the thermostat. The boiler itself is usually fine.
Check these first
These checks do not involve opening the boiler or any gas work.
- Wait a minute after a power cut. If the power has just come back on, give the units up to a minute to reconnect. Worcester’s instructions say to allow up to 1 minute after power up.
- Change the thermostat batteries. The Comfort II RF thermostat uses two AA (LR6) 1.5V alkaline batteries. Weak batteries are the most common cause of a lost signal, so fit fresh alkaline ones even if the display still shows.
- Check the boiler has power. If the receiver is plugged into the boiler, a boiler with no power means no receiver. Check the fused spur and the boiler display.
- Check the signal strength. On the Comfort II RF, hold the menu button for three seconds or more, turn the knob to Info, press it and select signal strength. Worcester’s scale runs from 0 to 10: 0 means no signal, 1 to 3 is weak, 4 to 6 acceptable and 7 to 10 very good.
- Move the thermostat if the signal is weak. Try it closer to the boiler to test. Worcester recommends mounting the thermostat on an inside wall, out of direct sunlight and draughts, away from radiators, and no closer than 300mm to metal objects, including metal wall boxes.
- Think about what has changed. New furniture, a mirror, a metal cabinet, a new wall or even a new appliance near the thermostat or receiver can weaken the signal.
If A21 clears but comes back often, the signal is marginal and the thermostat or receiver needs moving. Our boiler repair engineers can test the signal and reposition the controls if the checks above do not solve it.
What not to do
- Do not remove the boiler casing or covers to reach the receiver or wiring. Under the Gas Safety (Installation and Use) Regulations 1998 only a Gas Safe registered engineer may work on a gas appliance.
- Do not mix old and new batteries, or use rechargeable batteries unless your thermostat’s instructions allow them.
- Do not keep pressing buttons on the boiler hoping it clears. A21 is a communication problem, and resetting the boiler will not fix the signal.
- If you smell gas, call the National Gas Emergency Service on 0800 111 999, open windows, do not use electrical switches and turn off the gas at the meter if it is safe.
Pairing the thermostat and receiver again
The thermostat and receiver arrive already paired and normally connect by themselves when powered up. If they have lost their pairing, or one unit has been replaced, they need pairing again.
Worcester’s instructions for the Comfort II RF describe pairing as a two-part job: holding the override or pairing button on the receiver for 5 to 10 seconds until its light flashes, then selecting pairing from the Radio settings in the thermostat’s Installer menu. Pairing takes around a minute. If the pairing succeeds, the display shows which heating circuit the thermostat is linked to.
If your receiver is plugged into the boiler’s fascia and the button is not reachable without removing any covers, leave pairing to an engineer. If your thermostat is a different Worcester model, follow the instructions for that model, because menus and codes can differ between controls.
Common causes of A21
| Cause | What you might notice | Can you fix it yourself? | What the engineer does |
|---|---|---|---|
| Flat or weak batteries | Faint display, A21 on and off | Yes, fit new alkaline batteries | Nothing further needed |
| Power cut or boiler off | A21 after power returns | Yes, wait up to a minute | Checks power to the receiver if it stays |
| Weak signal | Low signal reading, A21 comes and goes | Often, by moving the thermostat | Repositions, or wall-mounts the receiver |
| Boiler in loft or garage | Poor signal from the start | No | Fits the receiver on a wall plate in a better spot |
| Metal or thick walls in the way | Signal drops after changes to the room | Sometimes | Tests signal in different positions |
| Lost pairing | A21 or A28 (not paired) | Sometimes, if the receiver button is accessible | Pairs the units again |
| Faulty thermostat or receiver | A21 persists with good batteries and a short distance | No | Tests both units and replaces the faulty one |
What an engineer will check
- Power to the receiver. The engineer confirms the receiver is powered and its light shows it is working.
- Signal strength. They check the reading from the current position and from other positions to find a reliable spot.
- Receiver position. Where the boiler is in a loft, garage or behind thick walls, Worcester’s instructions recommend wiring the receiver to a wall plate in a better position. The optional wall mounting kit places it at around 1.2 metres from the floor.
- Pairing. The units are unpaired and paired again if needed.
- The units themselves. If the signal is still lost at close range with fresh batteries, the thermostat or receiver is faulty and needs replacing.
- Wiring. Where the receiver connects to the boiler through a wired bus, the connection is checked. The Comfort II RF instructions list A27 for a failure to communicate with the boiler’s EMS bus.
If your controls are old or unreliable, it can be worth upgrading. Our smart thermostat installation page covers modern options that work with Worcester boilers.
Related Comfort II RF codes
The same Worcester instructions list these related codes:
- A22: loss of RF signal, as A21.
- A23: the room thermostat’s internal sensor has failed.
- A24: the remote RF unit has a fault.
- A25 and A26: pairing faults, such as no zone available or more than one thermostat paired to the same receiver.
- A27: unable to communicate with the boiler’s EMS bus.
- A28: not paired.
For codes shown by the boiler itself, see our guide to Worcester Bosch fault codes, including Worcester Bosch EA, the flame detection fault.
What we charge to fix it
Our prices, before you ring
| Weekday repair visit, Monday to Friday 8am to 5pm, no call-out fee | £150 + VAT £180 inc VAT |
| Evenings and weekends, first hour including the call-out | £297.60 inc VAT |
| Overnight, first hour including the call-out | £330 inc VAT |
| If a new boiler is the better answer, fitted | from £2,780 inc VAT |
The weekday visit is a fixed price. A Gas Safe engineer comes out, finds the fault and does any small fix that needs no parts, with up to an hour on site. If the repair needs parts or more time, you get a fixed price before anything else is done. We cover Hertfordshire, Bedfordshire, Cambridgeshire and North London. Book a boiler repair, see every rate, or get a new boiler price online.
Frequently asked questions
Is A21 a boiler fault?
No. A21 is shown by the wireless thermostat and means it has lost its radio link with the receiver. The boiler is usually working normally, but it is not receiving instructions from the thermostat.
Why does A21 keep coming back?
A code that clears and returns usually means a weak signal or failing batteries. Check the signal strength reading. If it is in the weak range, move the thermostat or have the receiver repositioned.
Can I use my heating while A21 is showing?
While the link is lost, the thermostat cannot control the boiler, so the heating may not come on when you expect. Fixing the link is the answer. If you are without heating and cannot restore it, call us for help.
Why did A21 appear after a power cut?
After the power returns, the thermostat and receiver need time to reconnect, and A21 shows until they do. Worcester’s instructions say to allow up to a minute. If it persists after that, check the batteries and signal.
Do I need a new thermostat for A21?
Not usually. Most A21 codes are cured by batteries, a better position or pairing. A new thermostat or receiver is only needed if one of them has failed.
When to call an engineer
If A21 is still showing after fresh batteries, a check of the signal strength and a move closer to the receiver, it needs an engineer to test the controls. We repair and service Worcester Bosch boilers and their controls across Hertfordshire, Bedfordshire and Cambridgeshire, and our phone is answered 24 hours a day, 7 days a week. Book a boiler repair or call 01462 506374.
Need help today?
Call and speak to a person, any hour, any day of the year, or get a fixed price quote online.
Get a fixed price quote Call 01462 506 374Rather have an engineer look at it?
Call the office, message us on WhatsApp or ask for a callback. We cover Hertfordshire, Bedfordshire and the surrounding areas.
What our customers say
Speak to a local engineer
Vantage Plumbing and Heating covers Hertfordshire, Bedfordshire and the surrounding areas. Call and talk to an engineer, or send us the details and we will come back to you with a price.
Gas Safe registered, number 956889. Emergency line answered 24/7.
Boiler engineers near you
Boiler playing up? Book a local Gas Safe engineer
We cover Hertfordshire, Bedfordshire and Cambridgeshire. Choose your town:
Not listed? See all the areas we cover or call 01462 506 374